Pump Station Drawdown Test Calculator

Measure a pump's actual capacity in the field from a wet-well drawdown test — no flowmeter — correcting for the inflow that keeps arriving while you pump. Runs entirely offline; inputs persist in this browser via localStorage.

Use limits: This assumes the wet-well plan area is constant over the test band — run the test between two elevations with straight walls, clear of benches, the influent pipe, and pump-off/on floats. Inflow rarely stops during a test; measure it (pump-off fill) or isolate it, because ignoring it understates the pump. Run several cycles and average, and confirm only the intended pump(s) were running.
Wet-Well Plan Area

Inflow (pump off)

With all pumps off, time how far the level rises — that's the inflow arriving.

Drawdown (pump on)

How the Numbers Are Derived

The drawdown test

With no flowmeter, a pump's capacity comes from how fast it empties a known volume. Plan area A times a level change d is a volume; divided by the time it took, it's a flow. In field units, Q (gpm) = 7.48 · A (ft²) · d (ft) / t (min) — the 7.48 converts cubic feet to gallons.

The catch is inflow. While the pump draws the well down, sewage keeps arriving, so the level falls slower than the pump is actually moving water. The net drawdown rate is Qpump − Qin. Measure the inflow first with the pumps off (time the level rise), then Qpump = (net drawdown rate) + Qin. Isolate the influent and Qin is zero and the net drawdown is the pump.

Field notes

References

  1. Recommended Standards for Wastewater Facilities (“Ten-State Standards”) — pump station testing.
  2. Hydraulic Institute / pump field-testing references. Companion tools: wet well cycle time and the pump system-curve plotter.