Weir & Orifice Flow Calculator

Temporary flow measurement during startup and testing: sharp-crested V-notch, rectangular, and Cipolletti weirs, plus submerged orifice. Runs entirely offline; inputs persist in this browser via localStorage.

Use limits: These formulas assume a properly built and installed sharp-crested weir with a free (aerated) nappe, or a clean sharp-edged orifice, and head measured correctly. A plywood weir with a rough edge, a drowned nappe, or a tape measure held at the crest reads confidently and wrong. Good field accuracy is ±5% under ideal conditions; treat results accordingly.
Device

Measure the water surface upstream of the weir, at least 4× the head back from the crest — not at the crest, where drawdown has already started.

How the Numbers Are Derived

Weir formulas (US units: Q in cfs, h and L in ft)

Conversions: 1 cfs = 448.83 GPM = 0.6463 MGD.

Conditions the formulas assume (the accuracy fine print)
Choosing a device in the field

References

  1. USBR, Water Measurement Manual — weir and orifice formulas, installation conditions. https://www.usbr.gov/tsc/techreferences/mands/wmm/
  2. ISO 1438 — Hydrometry: thin-plate weirs.