VFD “Hand vs. Auto” Rotation Matrix

Tracks observed motor rotation in Hand and Auto per equipment ID, and says whether the fix is a drive parameter or physical leads — before anyone opens the MCC. Runs entirely offline; the matrix persists in this browser via localStorage.

No equipment added yet.

How the Verdicts Are Derived

The one insight that saves the rework

Physical wiring affects Hand and Auto identically — the same three leads feed the same motor either way. So if rotation differs between Hand and Auto, wiring cannot be the cause: one of the two references is inverted in software (drive parameter, PLC output sign, or a reversed run command). Only when rotation is wrong in both modes is it a lead swap — and then the fix is swapping any two of the three phases at the MCC.

Verdict table

Reminder of why it matters: a three-phase centrifugal machine running backward delivers roughly half flow and head and often sounds nearly normal — it gets missed.

Test discipline

References

  1. The drive manufacturer's parameter manual — direction/reference parameters (governing document for the software side).
  2. Motor and driven-equipment O&M — rotation arrow and reverse-rotation restrictions.