Pipe Flushing & Scour Velocity Calculator

The flow needed to reach a target scour velocity in a water main — or the velocity a given flow achieves — plus pipe volume, flush duration, and total water used. Runs entirely offline; inputs persist in this browser via localStorage.

Use limits: Velocity is what scours a main, not flow — and it takes real velocity: roughly 2.5 ft/s to move loose sediment and air, and ~5 ft/s for the unidirectional scour that lifts tuberculation and biofilm. A single 2½-inch hydrant outlet passes only so much (often ~1,000–1,200 gpm at usable residual pressure), so a large main may not reach scour velocity from one hydrant — that's why unidirectional flushing isolates valves to force the flow down one pipe.
Pipe
Flow / Velocity

Flush until clear — often 2–3 pipe volumes, or per the spec / until turbidity and chlorine residual stabilize.

How the Numbers Are Derived

The formulas

Velocity and flow in a full pipe: V (ft/s) = 0.4085 · Q (gpm) / D (in)², and inverted, Q = 2.448 · V · D². Pipe volume is 0.0408 · D² gallons per foot of length (e.g. 2.6 gal/ft for 8-inch, 5.9 gal/ft for 12-inch). The flush duration to pass N pipe volumes at flow Q is t = N · (volume) / Q, and the total water used is N · volume.

Field notes

References

  1. AWWA C651 — Disinfecting Water Mains (flushing velocity and procedure).
  2. AWWA M17 / unidirectional flushing program guidance. Companion tool: chlorine dosing & disinfection calculator.